Introduction: Easy Generator to Home Hook Up
About: New content on my YouTube channel - consider subscribing! I heat with wood, fix broken things and love camping with my family. I'm a closet solar nerd, enjoy auctions, not scared to dumpster dive and love hi… More About More Cowbell »
A generator is a core component to many people's emergency preparedness plans. (Maybe you have a cool charcoal powered or a multi-fuel generator.) However many fail to think through how exactly they will power the items they want to run when the grid is down.
In June of 2012 my family experienced a 10 day power outage. It was eye opening. It was 100 degrees during the day with periods of heavy rain. I had to run a sump pump to keep my basement dry, a refrigerator, freezer for food preservation, a portable AC unit in the living room to protect my infant, we charged phones, and ran the wifi router. I had power cords everywhere. It was a pain. I decided then and there I would find a better way.
A generator transfer switch is the legal and proper way to power your home with an emergency generator. There are three main types: automatic, manual transfer sub panel and a breaker interlock. Each has varying degrees of complexity, benefits and expense.
Automatic transfer switches will sense a power loss, start your standby generator and automatically move your load to the generator. These are awesome - but very expensive and require a full time dedicated standby generator.
Manual transfer sub panel switches are good option. They are less expensive than the automatic transfer switches (Starting around $300) and can be used with a portable generator. They typically only cover a few breakers which was problematic for me.
Breaker Interlock is the option I chose. It is National Electric Code compliant and is in my opinion the least expensive and most flexible option. My setup cost was just under $150. In this setup you use a breaker to energize your existing breaker box. Switching it on is easy and safe. My wife did an unassisted dry run in under 5 min - which included getting the generator out of the building.
The breaker interlock system has come in very handy for us. We can turn on overhead lights, wash clothes and keep our food cold, charge our phones, run the internet and much more....all while keeping our doors and windows closed and no tripping on extension cords!
Disclaimer:
I am not an electrician. After much consulting and over sight from a licensed 25 year Master Electrician I believe these instructions to be correct and accurate for my jurisdiction. Electrical codes vary from place to place. In my place of residence home owners are allowed to do their own electrical work if it is up to code. You are responsible for any code violations, permits or awesome good stuff that comes from doing a project like this.
Step 1: NEVER DO THIS
I've listened to and have even seen people using a double male plug to energize their house during a power outage. This is dangerous.
- It is an electrical code violation.
- It is illegal in most places.
- It is a fire hazard. The power created by your generator is generally greater than the rating for the receptacle, wire and breaker.
- If you don't disconnect your main breaker it can shock the power company linemen - and you will get sued.
- You can easily get shocked because the male plug prongs are exposed.
Step 2: Determine Your Generator Plug Type and Amperage
First you have to figure out what type of amperage and plug type we are working with. You only want to do this on a generator with a big round plug. This will provide 220V (in the US) and power both sides of your breaker box. You will see the amperage written near the plug. Mine is a 30 Amp L-14-30.
For your convenience these are the most common sizes:
Nema L14-20 - 20 amp
Nema L14-30 - 30 amp
Nema CS6365 - 50 amp
Step 3: Supplies
Gather your supplies.
For the sake of this build we are going to assume you have a 30 amp plug on your generator - like the one shown. If your have one different please adjust your supplies.
Breaker interlock kit. Buy a UL rated device that fits your specific breaker box. These have been tested and validated to work. Many insurance companies and jurisdictions require the UL rating.
30 Amp 2 pole (double) breaker. Again you will need to buy one that fits your breaker box. All breakers are not the same.
Wire. I bought 10 feet of 10 gauge wire in black, red, green and white.
30 Amp power Inlet box.
Schedule 40 electrical conduit and fittings
Conduit body
Conduit glue
Flexible Non-Metallic Conduit and fittings (optional)
30 Amp generator extension cord. (Search Amazon for (your plug type) extension cord.)
Notice how all the amperage match. If you are using a 50 output on your generator you will need a 50 amp breaker, 50 amp power inlet box, a 50 amp extension cable and 8 gauge wire.
Step 4: Drill (or Find) Access Hole
Measure 5 times drill once.
My house had an conduit old hole in the foundation. Most people will need to drill one. A hammer drill is extremely helpful for making one. Try to get the conduit hole as close to the panel as you can.
Step 5: Mount Power Inlet Box
Remove the front cover from the power inlet box.
Remove a knock out and attach the PVC fitting. You can see here I opted for the water tight connector. Glue works just find too.
Using tapcons mount the power inlet box to the wall.
Step 6: Test Fit and Glue Conduit
Use a hack saw and cut the conduit to length.
Don't glue it until you know it fits. Once you are good glue it down.
Step 7: Wire the Generator Inlet Plug
Once the glue is dry we can start to work on the wiring.
Remove the cover on the conduit body. Pull the wires through one at a time attaching them to the plug as you go along. Remove about 3/4 of an inch of the insulation. Use a large flat screwdriver or a nut driver to tighten the terminals.
Green - Ground to the power inlet box.
White - Common, W terminal
Black and Red - Load - either X or Y terminal.
Step 8: Push Wiring Inside
Push the wires through the conduit into the house one at a time.
Replace the conduit body cover, checking proper fit of the gasket.
Fill any gaps between your conduit and the house with silicone or expanding foam.
Step 9: Prep Breaker Box for Wires
Turn off all the branch breakers and the main power breaker.
Remove the front panel of the breaker box by taking out the four screws.
Remove one knockout and screw in conduit adapter or in my case a blue non metallic conduit adapter.
Pull wires through conduit and into the box.
Step 10: Create Open Breaker Space
The breaker interlock method requires the to most upper and right breaker space to be free.
Generally you will need to move a breaker or two down. Most boxes will have enough spare wire to move things around a bit. If you do not have enough room and your breaker is 30 amps or less you can use a short piece of insulated wire and a wire nut.
DO NOT wire nut copper and aluminum wire together. They will corrode over time. You will need to pick up a wire splice at your local home store.
Step 11: Install Generator Breaker and Wires
Install your new breaker in the freed up space in the upper right of your breaker box.
The red wire goes to one terminal on the breaker and the black goes to the other.
The white wire goes to the common bond rail in the box.
The green wire goes to the ground rail.
Note: In a 2 wire home like mine - meaning no 3rd ground wire in the outlet box or the outlets in the home. It is acceptable in my jurisdiction to put the green ground wire to an open common terminal. It is not appropriate to use the ground wire for the common at the outlet.
Step 12: Install Breaker Retainer
Now it is time to lock down that breaker from moving. Install the retaining bracket. My retaining bolt was located between the main breakers and the 30 amp breaker.
Step 13: Install Inter Lock on Panel Cover
Flip the cover over and use the provided template.
Pre-drill the holes and then finish them out withe the bit size noted in your instructions.
Turn the panel back over and install the sliding interlock bolts.
Reinstall the panel with all the breakers in the off position. With the main in the off position turn the generator breaker to the on position. Ensure the interlock allows for the on position. You may have to shift the position of the panel cover.
Turn the generator breaker to the off position and drop the slide so it can not be turned on. Ensure the Main can be turned to the on position. Adjust panel cover if it will not.
If it does turn the breakers on one a at a time - with a 5 second delay between breakers. This will distribute the start up load.
Attach decals included in your kit to your breaker box and the outside service box.
Step 14: Operation
Time to load test! Write down these instructions and put them in your breaker box.
- Confirm power outage
- Place generator 15 feet from your home - with the exhaust pointing away from open windows and doors
- Start generator and ensure normal operating speed
- Attach generator extension cord to the generator with an inward push and gentle clockwise turn
- Attach extension cord to the home power inlet box with an inward push and a gentle clockwise turn
- At the breaker box turn off all the breakers
- Turn the main breaker off
- slide interlock up exposing the on position of the generator breaker - turn generator breaker on
- Turn on selected breakers with a 5 second delay in between each - ensuring the generator takes the load.
Avoid turning on HVAC, standard hot water heater and the stove unless your generator can handle it. As long as you can get past the initial start up load you can run a lot off of 30 amps.
Power off sequence:
- Turn off all branch breakers
- Turn off generator breaker
- Slide down generator interlock exposing the on position of the main breaker - turn main breaker on
- Turn on branch breakers one at a time with a 5 second delay between each one until they are all back on
- Power off generator and allow to cool
- Remove generator extension cord.
Enjoy your set up. It has come in very handy for us. We can turn on overhead lights, wash clothes and keep our foo
Participated in the
Automation Contest
Participated in the
Apocalypse Preparedness Contest
Participated in the
Tools Contest
8 People Made This Project!
DickR9 made it!
mtmtntop made it!
JeffT133 made it!
(Video) Easy DIY Generator Transfer Switch Install - Works with ANY Portable Gas or Battery GeneratorBruce steger made it!
See 4 More
Recommendations
373 Comments
7 years ago on Introduction
Great Job pointing out the suicide plug. Male to Male extension cords will kill you and burn down your house
Reply 5 years ago
You can follow a VERY simple procedure to not get electrocuted. Turn off power at the pole. Plug cable into receptacle and generator. Power up generator. I have a 220V 50A NEMA 14-50 plug outside my shop. The generator/welder has a 50A fused receptacle along with the 50 amp breaker for the 14-50. No fires or electrocution unless you previously were a candidate for a Darwin award.
Reply 5 years ago
Male-to-male plugs and cables cannot kill you unless you voluntarily unplug it with the power on! Be sure you know what you are doing and prevent anyone from handling the system under operation. My system uses such cable and has been working since 1995 (see my post above).
Reply 5 years ago
With electricity you can have intrinsic safety. Male - male plugs are like just leaving insulation off wires hoping no one will touch both....they are stupid.
Reply 5 years ago
Raymond the problem with male to male plugs is not killing yourself but killing the linemen trying to restore power as you backfeed power into the grid. Don't use them, they are dangerous and in many areas illegal.
Reply 5 years ago
Illegal yes unsafe not if you follow proper procedures. Use the 20 amp generator plug in on a 20amp electric cord plugged into a 20 amp circuit plug and shut off the main circuit breaker
Reply 5 years ago
Raymond do you have a post on how yours is setup?
Reply 5 years ago
Agree with Raymond, since you not doing stupid things it's may be quick pragmatic solution. When you are down - it's not a time to drill a hole in a wall with a hand-drill huh? :)
Reply 5 years ago
In a generator scenario, this is very true. But I also want to point out that a male to male can be useful in some situations. In my previous home my tv was wall mounted. It was a code violation and just an all around no-no to fish the power cable down through the wall. So I mounted 2 un-powered outlets one down low, one up high with the proper in-wall wiring, and made myself a male to male cord, going from my power conditioner/surge protector to the bottom outlet, thus powering the outlet up high behind the tv. It made for a safe installation and also provided surge protection for my tv that way.
Reply 5 years ago
If the generator has GFCI outlets, the male-to-male cord won't work. The GFCI breaker will trip.
7 years ago on Introduction
I generally shudder when I hear or see people try to set up a generator for all the reasons you point out. You did an excellent job and I like how you insure your generator is never tied into the grid. @ radiat1 I have used a similar system for about 5 years now my hots go through a transfer switch and my commons (white) are solid to the sub panel since the common and ground are tied together at your main panel if you were to send power to the common it would trip you generator breaker. I have had no problems and my number one concern is not killing a lineman.
Reply 5 years ago
Electrical generators can kill utility repairmen if powered on into the main. They must be isolated by a switch or breaker, and the main power switched out before the generator is powered on. That is why a transfer switch is better than breakers because it is designed and built for multiple operations using a strong double throw knife switch. I also recommend locking the transfer switch to prevent accidental or un authorized operation. Many transfer switches have special holes to fix the handle with a padlock.
Power utilities may have laws that requires an inspection and certification before the homeowner can use a generator, and can apply heavy fines if the installation is done or used without their approval.
1
7 years ago on Introduction
To More Cowbell, (love the name btw) As a veteran Master Electrician I just want to say "Well done". I just hope folks won't get lazy and put off the MOST important step in your article and that is the install of the "INTERLOCK". So easy to put that off because it will work without it but THAT is the killer if not done.
Reply 6 years ago
My main breaker is not in the breaker panel but is mounted on the opposite side of the house. How would you recommend I compensate for this?
Reply 6 years ago
you could mount a heavy duty 3 phase on off on toggle switch between the fuses of the main and the generator to the house fusebox you can do that near the housebox
http://www.bundupower.co.za/mcs.php
you can use it as the mainswitch between main and generator basicly it will switch between one , then off , then the other , never together / combined
Reply 5 years ago
Don't use such a switch. Buy a transfer switch certified and rated for the purpose. Home Depot still sells the same item I bought (see my post above) for $53 now. The store SKU is #100065.
Reply 6 years ago
The only problem with this is that the toggle switch would have to be listed and labeled for the application. I'm not sure you'll be able to find one.
Reply 6 years ago
the one i showed actually WAS for exactly that setup and was labeled gen and main
Reply 6 years ago
You can put a sub panel next to your breaker panel. In between the two, you can wire a transfer switch. Wire from a 2 pole breaker (sized according to your generator) to the transfer switch (like this one: http://www.homedepot.com/p/Reliance-Controls-60-A... Wire the generator to the other line input. Wire the sub panel to the load output side. Then move only the circuits that you want to be backed up by the generator from your original panel, to the new sub panel.
Follow all local codes and the NEC for securing, bonding, etc. and you should have no problems.