The Americans with Disabilities Act (ADA) specifies the minimum criteria for Accessible Doors in New Construction Accessible Buildings. According to the standard, Accessible Doors must be located:

  • At each accessible entrance to a building
  • At each accessible space within the building
  • Along all accessible routes within the building
  • At all Egress points

The standards state that a minimum of 50% of all public entrances to the building must be accessible, there must be at least one accessible entrance to all tenancies and the number of accessible entrances must be at least equivalent to the number of exits required by the building and/or fire codes. This percentage excludes specially considered accessible entrances such as those from parking garages, tunnels, or elevated walkways from which all entrances must be accessible. The requirements state, however, that it is preferable if ALL entrances are accessible.

The following rules apply in order for a door to be considered accessible:

  • A revolving door or turnstile cannot be the only means of passage at an accessible entrance or along an accessible route.
  • At least one side of any double-leaf doorways with independently operated doors must meet the criteria.
  • The minimum clear opening must be 32” with the door open 90°. This means that the door width must be approximately 34” or larger due to the thickness of the door. This is why a 36” door is commonly used excepting at metal bathroom stall partitions where the door is significantly thinner.
ADA Accessible Doors - An In-Depth Look at the Building Code - EVstudio (1)
  • Two doors in series must have a minimum of 48” in addition to the width of the door(s) swinging into the space (so a 36” door swinging into a hall would require the hall to be a minimum of 7’-0” long before any other door could be placed, if the second door does not also swing into the hall).
ADA Accessible Doors - An In-Depth Look at the Building Code - EVstudio (2)
  • Thresholds at accessible doorways cannot exceed ½” in height. Exterior sliding doors are excepted and allowed to have a threshold of up to ¾” in height. Raised thresholds must be beveled with a slope no greater than 1:2.
  • Accessible Door hardware and handles at accessible doors must have a shape that is easy to grasp with one hand and does not require tight grasping, pinching or twisting of the wrist to operate. Door handles must be no higher than 48” above the finished floor.
  • Door closers must be adjusted to take a minimum of 3 seconds to move 3 inches from a open position of 70°.
  • Accessible Doors should not take more than 5 pounds of force to open.
  • The door shallprovide the minimum maneuvering clearances detailed below:
    • When approaching a swinging door in a forward direction from the pull side, there should be a min. of 18” of wall (24” preferred) on the latch side of the door and 60” min. of clear floor in front of the door.
    ADA Accessible Doors - An In-Depth Look at the Building Code - EVstudio (3)
    • When approaching a swinging door in a forward direction from the push side, there should be a min. of 48” clear in front of the door. There should also be a min. of 12” of wall on the latch side if the door has both a closer and latch. If the door does not have both a closer and latch, there is no minimum wall requirement.
    ADA Accessible Doors - An In-Depth Look at the Building Code - EVstudio (4)
    • For a hinge-side approach on the pull side of a swinging door, there must be a min. of 60” clear in front of the door and 36” of wall to the latch side of the door. If there is a min. of 42” of wall to the handle side of the door, then the min. clear space in front of the door may be reduced to a min. of 54”.
    ADA Accessible Doors - An In-Depth Look at the Building Code - EVstudio (5)
    • For a hinge-side approach on the push side of a swinging door, there must be a clear space in front of the door that measures 54”x42”. The clear space must measure a min. of 54”x48” if the door includes both a closer and a latch. This diagram does not have a min. requirement beside the door on the latch side, and so the clear space box may slide left or right as necessary in front of the door in this scenario.
    ADA Accessible Doors - An In-Depth Look at the Building Code - EVstudio (6)
    • For a latch-side approach on the pull side of a swinging door, there must be a min. of 48” (54” if the door also has a closer) of clear space in front of the door and a min. of 24” of wall on the latch side of the door.
    ADA Accessible Doors - An In-Depth Look at the Building Code - EVstudio (7)
    • For a latch-side approach on the push side of a swinging door, there must be a min. of 42” (48” if the door also has a closer) of clear space in front of the door and a min. of 24” of wall on the latch side of the door.
    ADA Accessible Doors - An In-Depth Look at the Building Code - EVstudio (8)
    • A front approach to a sliding or folding door only requires that there is a min. of 48” clear space in front of the door.
    ADA Accessible Doors - An In-Depth Look at the Building Code - EVstudio (9)
    • A slide-side approach to a sliding or folding door requires a clear space in front of the door measuring a min. of 54”x42”. Again, this diagram does not have a min. requirement beside the door on the latch side, and so the clear space box may slide left or right as necessary in front of the door in this scenario.
    ADA Accessible Doors - An In-Depth Look at the Building Code - EVstudio (10)
    • A latch-side approach to a sliding of folding door requires a min. 42” clear space in front of the door and a min. of 24” of wall on the latch-side of the door.

    ADA Accessible Doors - An In-Depth Look at the Building Code - EVstudio (11)

  • Automatic or Power Assisted Doors must comply with the A156.10-1995 Standard published by ANSI/BHMA (American National Standards Institute / Builders Hardware Manufacturer’s Association).

These are just the requirements for doorways for “Accessible Spaces”. There are additional requirements, including doors, for Accessible restrooms and toilet stalls. According to the 2004 Guidelines, Accessible Spaces are:

All areas of newly designed and newly constructed buildings and facilities and altered portions of existing buildings and facilities shall comply with these requirements.

However,

These requirements are to be applied to all areas of a facility unless exempted, or where scoping limits the number of multiple elements required to be accessible. For example, not all medical care patient rooms are required to be accessible; those that are not required to be accessible are not required to comply with these requirements. However, common use and public use spaces such as recovery rooms, examination rooms, and cafeterias are not exempt from these requirements and must be accessible.

In general, it is best to simply assure that ALL public spaces within a building are designed for accessibility. In addition to the ADA Guidelines, there are also accessibility standards published by the American National Standards Institute (ANSI). Most jurisdictions tend to use the ADA Guidelines but this isn’t always the case. If in doubt, however, about the specific requirements for your project, it is best to check directly with the local municipality having jurisdiction over the project.

  • EVstudio AEP
  • November 13, 2009
  • Architectural process, Building Technology, Commercial, FAQ, News, Research

Author

EVstudio AEP

Articles

Article Categories

14 thoughts on “ADA Accessible Doors – An In-Depth Look at the Building Code”

  1. ADA Accessible Doors - An In-Depth Look at the Building Code - EVstudio (14)

    Bill Foster

    March 16, 2016 at 2:01 pm

    Alan,

    There are very few scenarios where doors would not have to be accessible in a new building that is not a private residence. Some of these scenarios include areas where only service technicians would be going such as crawlspaces and attics. I’ve seen exceptions for small platforms and for specific employee only access areas but most permitting jurisdictions take a very strict view on making most areas that customers OR employees use accessible.

    Thanks!

    Bill Foster
    Director of Architecture

  2. ADA Accessible Doors - An In-Depth Look at the Building Code - EVstudio (15)

    alan Ruano

    March 9, 2016 at 2:50 pm

    I am bidding Commercial Doors for a private Storage warehouse Company. Because this is not publicly accessible, do I not have to meet all the ADA Requirements for these doors ??

  3. ADA Accessible Doors - An In-Depth Look at the Building Code - EVstudio (16)

    Sean O'Hara

    August 5, 2015 at 3:31 pm

    Eileen, are you saying that the only means of egress is through the garage? No front door. If that is the case its wouldn’t work under the IRC.

    R311.1 Means of egress. All dwellings shall be provided
    with a means of egress as provided in this section. The means
    of egress shall provide a continuous and unobstructed path of
    vertical and horizontal egress travel from all portions of the
    dwelling to the exterior of the dwelling at the required egress
    door without requiring travel through a garage.

  4. ADA Accessible Doors - An In-Depth Look at the Building Code - EVstudio (17)

    Eileen Holz

    July 17, 2015 at 4:31 pm

    My city is building its 1st 2-bedroom accessible unit. They are telling me that there will be only one access—through the garage. I say that when I built my accessible townhome I was required to put an outside entry (to the patio) in my bedroom so if there was a fire in the front of my townhome I could still get out. I don’t think a single entry into a garage where many fires start is allowable as the only access. Comments or direction or code please.

  5. ADA Accessible Doors - An In-Depth Look at the Building Code - EVstudio (18)

    February 20, 2014 at 1:08 pm

    Gentlemen:

    A Question…..do stair doors need to have push and pull clearaneces? For example, for occupancies with less than 50, and a sprinkler system, the stair width can be be as little as 36″ between stringers. Does the stair landing then need to be wider to handle the pull side clearance or is a 36″ landing acceptable?

    Thank you in advance for your consideration!

    Phil Kiester

  6. Pingback: The 3 Most handicapped-UNfriendly Construction Curses of Chicago « The Handicapped Chicagoan

  7. ADA Accessible Doors - An In-Depth Look at the Building Code - EVstudio (20)

    Sean O'Hara

    December 10, 2009 at 1:44 pm

    Stuart, that should work, I would just verify with your inspector before you make a purchase in case your local codes have any further requirements.

  8. ADA Accessible Doors - An In-Depth Look at the Building Code - EVstudio (21)

    stuart pollock

    December 10, 2009 at 9:23 am

    For a door with a closer and latch from the push side requires a 12 inch clearance to a wall on the latch side. If panic hardware is provided, can this eliminate the requirement for the 12 inch clearance?

  9. ADA Accessible Doors - An In-Depth Look at the Building Code - EVstudio (22)

    November 21, 2009 at 7:02 pm

    A freind and I have put together an online form where you can check if your door is ADA compliant, it may help you determine if your existing door or if your redesign meets the standards. If you try it out plase send some feed back and let us know what you think.; go to http://www.AdaResults.com and give it a shot.

  10. ADA Accessible Doors - An In-Depth Look at the Building Code - EVstudio (23)

    Sean O'Hara

    November 13, 2009 at 9:55 am

    Unless you only ever do one very specific project type you really have to run through the analysis of what codes apply every time. The boundaries are not always obvious.

  11. ADA Accessible Doors - An In-Depth Look at the Building Code - EVstudio (24)

    November 13, 2009 at 7:42 am

    Navigating all of the different codes and knowing when to use each one is not often the easiest of tasks. Thanks for the additional info Sean!

  12. ADA Accessible Doors - An In-Depth Look at the Building Code - EVstudio (25)

    Sean O'Hara

    November 12, 2009 at 3:42 pm

    ANSI is often the code cited in the International Building Code, so you generally have to read both requirements. Also important to know that ADA only applies to commercial buildings and places of public accommodation. Buildings that fall in the IRC (single family and duplexes) avoid both but residential multifamily buildings will see portions of ANSI.

Comments are closed.

Related Articles

Certified Reversible Buildings

Dean Dalvit

Qualification for Reversible Building Manufacturers

Dean Dalvit

Reversible Building General Contractors

Dean Dalvit

Trending Articles

Toilet/Water Closet Wall Clearances and Space In Front by Evstudio

ADA Accessible Doors – An In-Depth Look at the Building Code by EVstudio AEP

Interpreting Truss Shop Drawing Dimensions by Evstudio

Popular Articles

Cost per Square Foot of Commercial Construction by Region by Dean Dalvit

Construction Types V-A and V-B in the International Building Code by Sean O'Hara

Type A vs. Type B in Residential Design by EVstudio AEP

About EVstudio

EVstudio is a full-service in-house design firm specializing in architecture, engineering, planning, and other design services for commercial and residential projects.

Learn More

Contact EVstudio

Interested in learning more?

Contact Us

<< Back to Articles

ADA Accessible Doors - An In-Depth Look at the Building Code - EVstudio (2024)
Top Articles
Latest Posts
Recommended Articles
Article information

Author: Tish Haag

Last Updated:

Views: 6285

Rating: 4.7 / 5 (67 voted)

Reviews: 90% of readers found this page helpful

Author information

Name: Tish Haag

Birthday: 1999-11-18

Address: 30256 Tara Expressway, Kutchburgh, VT 92892-0078

Phone: +4215847628708

Job: Internal Consulting Engineer

Hobby: Roller skating, Roller skating, Kayaking, Flying, Graffiti, Ghost hunting, scrapbook

Introduction: My name is Tish Haag, I am a excited, delightful, curious, beautiful, agreeable, enchanting, fancy person who loves writing and wants to share my knowledge and understanding with you.